HAWPD Series – High Accuracy Differential Pressure Transmitter

Excellent long-term stability and high accuracy
Backlit LCD for display of differential or gauge pressure
Jumper selectable LCD backlight for low power consumption applications
Four switch selectable pressure ranges
Jumper selectable output types, 4-20 mA, 0-5 and 0-10 Vdc
NEMA 4X (IP65) enclosure
Pushbutton and remote zeroing terminal
Uni-directional or bi-directional pressure range selection switch
High / low port swap switch to solve incorrect plumbing for differential
Normal/slow surge damping switch to prevent false alarms and reduce noise
Output polarity reverse switch

Categories: ,

Product Description

The HAWP-D Series has been discontinued and has been replaced by the HADP Series.

The HAWP-D series high accuracy differential pressure transmitter is designed with dual sensors that enable it to accept high differential pressures in the ranges of 5PSI to 500PSI. All models can handle overload pressure 2X the maximum full scale range and burst pressure is 5X the maximum full scale range.

Features include field selectable pressure ranges and output signal types for the most flexible applications. Typical HVAC applications include monitoring of water differential and gage pressure. The output signal is factory calibrated and temperature compensated for the highest start-up accuracy.

Valve Bracket option not available in the USA.

pdf-icon Brochure

pdf-icon Submittal

pdf-icon Install

pdf-icon

 Manifold Install